WALL-MOUNT 4 & 7 CHANNEL SCANNER

FEATURES

POWERFUL DISPLAY MODES

FULLY PROGRAMMABLE

WIDE RANGE OF INPUTS

MULTIPLE ALARM OPTIONS

SPECIFICATIONS

INPUT TYPE:
Input types: J,K,T,E,R,S,B, RTD & Thermistor,
4-20ma, 0-50ma, 0-5vdc, 0-10vdc
Cold junction comp. error: +/- 1C Max (10 to 40C)
Open thermocouple indication: HELP displayed.
Custom inputs available: Consult factory
SCAN RATE/ DISPLAY TIME:
Fixed: Two channels per second.
Display time: Programmable from 1-9999 seconds.
RELIABILITY/ACCURACY:
Calibration: NIST traceable (temperature)
Resolution: 1 degree C or F , Thermistor = 0.1 C/0.2F
Selectable display units:: Centigrade or Fahrenheit
ANALOG TO DIGITAL CONVERSION:
20,000 count A/D converter
Dual slope integrating converter.
Conversion rate: Seven conversions/sec (typical)
DISPLAY:
Red 7-segment LED display, 0.8 inch (20mm) height
Negative polarity indication. Over-range indication: HELP
Display test: Briefly indicates 8.8.8.8.8.8.8. on power up
ELAPSED TIME:
Displayed in hours, minutes & seconds. Format: HH.MM.SS
POWER OPTION:
120VAC -- 60 Hz (Standard) 220VAC -- 50 HZ (Opt)
8VDC -- 12VDC @ 900ma (optional)
RELAY/OPEN COLLECTOR OUTPUT:
Relays: Single pole single throw, 1 amp @ 28vdc or 0.5 amp @120vac
Open Collector output: 50ma max (internal 5vdc source).
DIMENSIONS:
Case: 7.55" W x 6.29" H x 4.05" D
Ingress Protectoin: up to IP65 (DIN standard)